DMXPathfinder LR Installation & Assembly
39
the same rack, allow for at least a 1U vent panel at the top and bottom of the
rack.
Power Requirements -- A single phase power source (50 or 60Hz, 100-
240VAC, at 0.1A per Input Module and 0.25A per Output Module) must be
provided to the DMXPathfinder LR equipment rack. It is recommended that no
more than ten I/O modules be connected to one power circuit due to the startup
current requirements of their switch-mode power supplies.
RACK SIZING AND PLACEMENT
The system installer normally supplies the DMXPathfinder LR equipment
rack. Use only a standard E.I.A. 19" rack, at least 18" deep (24" is
recommended). To calculate minimum height, add up the number of 2U Input
Vedere la pagina 39